(Created page with "=== Modbus Registers === Below is a list of available MODBUS registers. The same register numbers are also used by the MIOS-2 protocol. === Modbus Read / Write (0x17) Functio...")
 
 
(One intermediate revision by the same user not shown)
Line 53: Line 53:
 
| COIL Relay 10 || DI#13 || bit || R || 3013
 
| COIL Relay 10 || DI#13 || bit || R || 3013
 
|-
 
|-
| Inputs || DI#16 - DI#01 || u16 || R || 0x0000 - 0x0FFF || 3001
+
| Inputs || DI#16 - DI#01 || u16 || R || 0x0000 - 0x1FFF || 3001
 
|}
 
|}
  
Line 84: Line 84:
 
|-
 
|-
 
| Outputs || DO#16 - DO#01 || u16 || RW || 0x0000 - 0x03FF || 4001
 
| Outputs || DO#16 - DO#01 || u16 || RW || 0x0000 - 0x03FF || 4001
 +
|}
  
 
{{Note|NoteText=
 
{{Note|NoteText=
 
To activate the '''bootloader''', it is necessary to write a value 617 into the registry with an offset 1204 and restart the device.
 
To activate the '''bootloader''', it is necessary to write a value 617 into the registry with an offset 1204 and restart the device.
 
}}
 
}}

Latest revision as of 12:28, 24 February 2020

Modbus Registers

Below is a list of available MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.

Modbus Read / Write (0x17) Function

METEL IO modules have implemented the MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for:

1. Writing of outputs via MODBUS function (0x16) Writing Multiple Registers

2. Reading of inputs via MODBUS function (0x03) Read Holding Registers


This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the reading and writing of outputs. This requires a total of 2 frames to be sent over MODBUS.


Default Settings of Communication

Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1

Subject Channel Type R/W Value Offset
States of
Digital
Inputs and
Relay
Outputs
Digital Input 1, 230V DI#01 bit R 0 = inactive
1 = active
3001
Digital Input 2, 230V DI#02 bit R 3002
Digital Input 3, 230V DI#03 bit R 3003
COIL Relay 1 DI#04 bit R 3004
COIL Relay 2 DI#05 bit R 3005
COIL Relay 3 DI#06 bit R 3006
COIL Relay 4 DI#07 bit R 3007
COIL Relay 5 DI#08 bit R 3008
COIL Relay 6 DI#09 bit R 3009
COIL Relay 7 DI#10 bit R 3010
COIL Relay 8 DI#11 bit R 3011
COIL Relay 9 DI#12 bit R 3012
COIL Relay 10 DI#13 bit R 3013
Inputs DI#16 - DI#01 u16 R 0x0000 - 0x1FFF 3001
Subject Channel Type R/W Value Offset
Relay
Outputs
Relay Output 1 DO#01 bit RW 0 = inactive
1 = active
4001
Relay Output 2 DO#02 bit RW 4002
Relay Output 3 DO#03 bit RW 4003
Relay Output 4 DO#04 bit RW 4004
Relay Output 5 DO#05 bit RW 4005
Relay Output 6 DO#06 bit RW 4006
Relay Output 7 DO#07 bit RW 4007
Relay Output 8 DO#08 bit RW 4008
Relay Output 9 DO#09 bit RW 4009
Relay Output 10 DO#10 bit RW 4010
Outputs DO#16 - DO#01 u16 RW 0x0000 - 0x03FF 4001

Note: To activate the bootloader, it is necessary to write a value 617 into the registry with an offset 1204 and restart the device.