Difference between revisions of "IF-11"
(Created page with "=== Modbus Registers === Below is a list of available MODBUS registers. The same register numbers are also used by the MIOS-2 protocol. === Modbus Read / Write (0x17) Functio...") |
|||
Line 24: | Line 24: | ||
}} | }} | ||
− | <!-- MODBUS "IF- | + | <!-- MODBUS "IF-11 States of Inputs" registers table --> |
{| class="wikitable" | {| class="wikitable" | ||
|- | |- | ||
Line 30: | Line 30: | ||
! colspan="2" | Subject !! style="width: 110px;" | Channel !! style="width: 30px;" | Type !! style="width: 30px;" | R/W !! style="width: 230px;" | Value !! style="width: 60px;" | Offset | ! colspan="2" | Subject !! style="width: 110px;" | Channel !! style="width: 30px;" | Type !! style="width: 30px;" | R/W !! style="width: 230px;" | Value !! style="width: 60px;" | Offset | ||
|- | |- | ||
− | | rowspan="4" style="width: 90px;" | <span style="font-size: 17px;"> '''IF- | + | | rowspan="4" style="width: 90px;" | <span style="font-size: 17px;"> '''IF-11 <br /> States of <br /> Inputs''' </span> |
|| Balanced Input 1 (bin) || DI#33 || bit || R || rowspan="2" | 0 = inactive <br /> 1 = active || 3033 | || Balanced Input 1 (bin) || DI#33 || bit || R || rowspan="2" | 0 = inactive <br /> 1 = active || 3033 | ||
|- | |- |
Revision as of 05:01, 17 April 2020
Modbus Registers
Below is a list of available MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.
Modbus Read / Write (0x17) Function
METEL IO modules have implemented the MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for:
1. Writing of outputs via MODBUS function (0x16) Writing Multiple Registers
2. Reading of inputs via MODBUS function (0x03) Read Holding Registers
This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the reading and writing of outputs. This requires a total of 2 frames to be sent over MODBUS.
Default Settings of Communication
Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1
Note: The MODBUS address is the same as the address of the main device of which the IF module is part.
Subject | Channel | Type | R/W | Value | Offset | |
---|---|---|---|---|---|---|
IF-11 States of Inputs |
Balanced Input 1 (bin) | DI#33 | bit | R | 0 = inactive 1 = active |
3033 |
Balanced Input 2 (bin) | DI#34 | bit | R | 3034 | ||
Balanced Input 1 | AI#33 | u16 | R | 1000 = 1000Ω 0 = 0Ω |
5033 | |
Balanced Input 2 | AI#34 | u16 | R | 5034 |