Difference between revisions of "IF-15"
(Created page with "=== Modbus Registers === Below is a list of available MODBUS registers. The same register numbers are also used by the MIOS-2 protocol. === Modbus Read / Write (0x17) Functio...") |
|||
(One intermediate revision by the same user not shown) | |||
Line 30: | Line 30: | ||
! colspan="2" | Subject !! style="width: 110px;" | Channel !! style="width: 30px;" | Type !! style="width: 30px;" | R/W !! style="width: 230px;" | Value !! style="width: 60px;" | Offset | ! colspan="2" | Subject !! style="width: 110px;" | Channel !! style="width: 30px;" | Type !! style="width: 30px;" | R/W !! style="width: 230px;" | Value !! style="width: 60px;" | Offset | ||
|- | |- | ||
− | | rowspan=" | + | | rowspan="5" style="width: 90px;" | <span style="font-size: 17px;"> '''IF-15(G) <br /> States of <br /> Inputs''' </span> |
− | || Open Collector 1 || DO#33 || bit || | + | || Open Collector 1 || DO#33 || bit || RW || rowspan="4" | 0 = inactive <br /> 1 = active || 4033 |
|- | |- | ||
− | | style="width: 120px;" | Open Collector 2 || DO#34 || bit || | + | | style="width: 120px;" | Open Collector 2 || DO#34 || bit || RW || 4034 |
|- | |- | ||
− | | Open Collector 3 || DO#35 || bit || | + | | Open Collector 3 || DO#35 || bit || RW || 4035 |
|- | |- | ||
− | | Open Collector 4 || DO#36 || bit || R || | + | | Open Collector 4 || DO#36 || bit || RW || 4036 |
+ | |- | ||
+ | | Outputs || DI#33 - DI#48 || u16 || R || 0x0000 - 0x000F || | ||
|} | |} |
Latest revision as of 05:48, 17 April 2020
Modbus Registers
Below is a list of available MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.
Modbus Read / Write (0x17) Function
METEL IO modules have implemented the MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for:
1. Writing of outputs via MODBUS function (0x16) Writing Multiple Registers
2. Reading of inputs via MODBUS function (0x03) Read Holding Registers
This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the reading and writing of outputs. This requires a total of 2 frames to be sent over MODBUS.
Default Settings of Communication
Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1
Note: The MODBUS address is the same as the address of the main device of which the IF module is part.
Subject | Channel | Type | R/W | Value | Offset | |
---|---|---|---|---|---|---|
IF-15(G) States of Inputs |
Open Collector 1 | DO#33 | bit | RW | 0 = inactive 1 = active |
4033 |
Open Collector 2 | DO#34 | bit | RW | 4034 | ||
Open Collector 3 | DO#35 | bit | RW | 4035 | ||
Open Collector 4 | DO#36 | bit | RW | 4036 | ||
Outputs | DI#33 - DI#48 | u16 | R | 0x0000 - 0x000F |