Difference between revisions of "AI8.1"
Line 15: | Line 15: | ||
Stop bits: 1 <br /> | Stop bits: 1 <br /> | ||
+ | <!-- MODBUS Measured Voltage Values registers table --> | ||
{| class="wikitable" | {| class="wikitable" | ||
|- | |- | ||
Line 39: | Line 40: | ||
|- | |- | ||
| Analog Input 8 || AI#08 || s16 || R || 5008 | | Analog Input 8 || AI#08 || s16 || R || 5008 | ||
+ | |} | ||
+ | |||
+ | <!-- MODBUS Measured Current Values registers table --> | ||
+ | {| class="wikitable" | ||
+ | |- | ||
+ | |- style="font-size: 17px;" | ||
+ | ! colspan="2" | Subject !! Channel !! Type !! R/W !! Value !! Offset | ||
+ | |||
+ | |- | ||
+ | | rowspan="8"| <span style="font-size: 17px;"> '''Measured <br /> Current <br /> Values''' </span> | ||
+ | || Analog Input 1 || AI#11 || s16 || R || rowspan="8"| 1000 = 1 V <br /> 0 = 0 V <br /> -1000 = -1 V <br /> 32767 = upper range limit exceeded <br /> -32767 = lower range limit exceeded | ||
+ | || 5011 | ||
+ | |||
+ | |- | ||
+ | | Analog Input 2 || AI#12 || s16 || R || 5012 | ||
+ | |- | ||
+ | | Analog Input 3 || AI#13 || s16 || R || 5013 | ||
+ | |- | ||
+ | | Analog Input 4 || AI#14 || s16 || R || 5014 | ||
+ | |- | ||
+ | | Analog Input 5 || AI#15 || s16 || R || 5015 | ||
+ | |- | ||
+ | | Analog Input 6 || AI#16 || s16 || R || 5016 | ||
+ | |- | ||
+ | | Analog Input 7 || AI#17 || s16 || R || 5017 | ||
+ | |- | ||
+ | | Analog Input 8 || AI#18 || s16 || R || 5018 | ||
|} | |} |
Revision as of 09:01, 18 July 2018
Modbus Registers
Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.
Modbus Read / Write (0x17) Function
METEL IO modules have implemented MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for: 1) Writing of outputs via MODBUS function (0x16) Write Multiple Registers 2) Reading of inputs via MODBUS function (0x03) Read Holding Registers This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the writing and reading of outputs. This requires a total of 2 frames to be sent over MODBUS.
Default Settings of Communication
Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1
Subject | Channel | Type | R/W | Value | Offset | |
---|---|---|---|---|---|---|
Measured Voltage Values |
Analog Input 1 | AI#01 | s16 | R | 1000 = 1 V 0 = 0 V -1000 = -1 V 32767 = upper range limit exceeded -32767 = lower range limit exceeded |
5001 |
Analog Input 2 | AI#02 | s16 | R | 5002 | ||
Analog Input 3 | AI#03 | s16 | R | 5003 | ||
Analog Input 4 | AI#04 | s16 | R | 5004 | ||
Analog Input 5 | AI#05 | s16 | R | 5005 | ||
Analog Input 6 | AI#06 | s16 | R | 5006 | ||
Analog Input 7 | AI#07 | s16 | R | 5007 | ||
Analog Input 8 | AI#08 | s16 | R | 5008 |
Subject | Channel | Type | R/W | Value | Offset | |
---|---|---|---|---|---|---|
Measured Current Values |
Analog Input 1 | AI#11 | s16 | R | 1000 = 1 V 0 = 0 V -1000 = -1 V 32767 = upper range limit exceeded -32767 = lower range limit exceeded |
5011 |
Analog Input 2 | AI#12 | s16 | R | 5012 | ||
Analog Input 3 | AI#13 | s16 | R | 5013 | ||
Analog Input 4 | AI#14 | s16 | R | 5014 | ||
Analog Input 5 | AI#15 | s16 | R | 5015 | ||
Analog Input 6 | AI#16 | s16 | R | 5016 | ||
Analog Input 7 | AI#17 | s16 | R | 5017 | ||
Analog Input 8 | AI#18 | s16 | R | 5018 |