Difference between revisions of "DI8.1"

From IPLOG
Jump to: navigation, search
Line 14: Line 14:
 
Data bits: 8 <br />
 
Data bits: 8 <br />
 
Stop bits: 1 <br />
 
Stop bits: 1 <br />
 +
 +
 +
 +
 +
 +
<!-- MODBUS "Device Identification" registers table -->
 +
{| class="wikitable"
 +
|-
 +
|- style="font-size: 17px;"
 +
! colspan="2" | Subject !! Type !! R/W !! style="width: 230px;" | Value !! style="width: 60px;" | Offset
 +
|-
 +
| rowspan="12" style="width: 90px;" | <span style="font-size: 17px;"> '''Device <br /> Identity''' </span>
 +
|| Product Type || u8[3] || R || || 1002-04
 +
|-
 +
| style="width: 215px;" | Serial Number || u32 || R || || 1005-06
 +
|-
 +
| PCB Version || u32 || R || || 1007-08
 +
|-
 +
| PCB Revision || u16 || R || || 1009
 +
|-
 +
| FW Version Major || u16 || R || || 1010
 +
|-
 +
| FW Version Minor || u16 || R || || 1011
 +
|-
 +
| FW Version - Revision || u32 || R || || 1012-13
 +
|-
 +
| IF#01 Slot State || u16 || R || 0 = N/A <br /> 1 = IF#01 not Inserted <br /> 2 = IF#01 Inserted, CRC error <br /> 3 = IF#01 Inserted, CRC OK || 1021
 +
|-
 +
| IF#01 Product Type || u8[3] || R || || 1022-24
 +
|-
 +
| IF#01 Serial Number || u32 || R || || 1025-26
 +
|-
 +
| IF#01 PCB Version || u32 || R || || 1027-28
 +
|-
 +
| IF#01 PCB Revision || u16 || R || || 1029
 +
|-
 +
| rowspan="3" style="width: 90px;" | <span style="font-size: 17px;"> '''Device <br /> Control''' </span> || Reset || u16 || RW || 55203 = To Reboot || 1201
 +
|-
 +
| Bootloader / Application || u16 || R || 0x00A – Application, <br /> 0x00B – Bootloader || 1203
 +
|-
 +
| Restart to Bootloader || u16 || RW || 617 = To Bootloader <br /> else = deactivate <br /> bootloader || 1204
 +
|-
 +
| rowspan="2" style="width: 90px;" | <span style="font-size: 17px;"> '''Device <br /> Status''' </span> || Board Power Voltage || u16 || R || 105 = 10,5V || 1311
 +
|-
 +
| Board Temperature || u16 || R || -200 = -20,0°C <br /> 250 = 25,0°C || 1321
 +
|}
 +
 +
{{Note|NoteText=
 +
To activate the '''bootloader''', it is necessary to write a value 617 in to the registry with offset 1204 and restart the device.
 +
}}

Revision as of 08:08, 19 July 2018

Modbus Registers

Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.

Modbus Read / Write (0x17) Function

METEL IO modules have implemented MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for: 1) Writing of outputs via MODBUS function (0x16) Write Multiple Registers 2) Reading of inputs via MODBUS function (0x03) Read Holding Registers This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the writing and reading of outputs. This requires a total of 2 frames to be sent over MODBUS.

Default Settings of Communication

Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1



Subject Type R/W Value Offset
Device
Identity
Product Type u8[3] R 1002-04
Serial Number u32 R 1005-06
PCB Version u32 R 1007-08
PCB Revision u16 R 1009
FW Version Major u16 R 1010
FW Version Minor u16 R 1011
FW Version - Revision u32 R 1012-13
IF#01 Slot State u16 R 0 = N/A
1 = IF#01 not Inserted
2 = IF#01 Inserted, CRC error
3 = IF#01 Inserted, CRC OK
1021
IF#01 Product Type u8[3] R 1022-24
IF#01 Serial Number u32 R 1025-26
IF#01 PCB Version u32 R 1027-28
IF#01 PCB Revision u16 R 1029
Device
Control
Reset u16 RW 55203 = To Reboot 1201
Bootloader / Application u16 R 0x00A – Application,
0x00B – Bootloader
1203
Restart to Bootloader u16 RW 617 = To Bootloader
else = deactivate
bootloader
1204
Device
Status
Board Power Voltage u16 R 105 = 10,5V 1311
Board Temperature u16 R -200 = -20,0°C
250 = 25,0°C
1321

Note: To activate the bootloader, it is necessary to write a value 617 in to the registry with offset 1204 and restart the device.