Difference between revisions of "AI8.1"
(Created page with "== Modbus Registers == Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol. == Modbus Read / Write (0x17) Fun...") |
|||
Line 1: | Line 1: | ||
− | == Modbus Registers == | + | === Modbus Registers === |
Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol. | Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol. | ||
− | == Modbus Read / Write (0x17) Function == | + | === Modbus Read / Write (0x17) Function === |
METEL IO modules have implemented MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for: | METEL IO modules have implemented MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for: | ||
1) Writing of outputs via MODBUS function (0x16) Write Multiple Registers | 1) Writing of outputs via MODBUS function (0x16) Write Multiple Registers | ||
Line 8: | Line 8: | ||
This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the writing and reading of outputs. This requires a total of 2 frames to be sent over MODBUS. | This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the writing and reading of outputs. This requires a total of 2 frames to be sent over MODBUS. | ||
− | == Default Settings of Communication == | + | === Default Settings of Communication === |
− | Device ID: 1 | + | Device ID: 1 <br /> |
− | Baudrate: 115 200 | + | Baudrate: 115 200 <br /> |
− | Parity: None | + | Parity: None <br /> |
− | Data bits: 8 | + | Data bits: 8 <br /> |
− | Stop bits: 1 | + | Stop bits: 1 <br /> |
+ | |||
+ | {| class="wikitable" | ||
+ | |- | ||
+ | ! colspan="2" | Subject !! Channel !! Type !! R/W !! Value !! Offset | ||
+ | |- | ||
+ | | rowspan="8"|Measured <br /> Voltage <br /> Values || Analog Input 1 || AI#01 || s16 || R || rowspan="8"| 1000 = 1 V <br /> 0 = 0 V <br /> -1000 = -1 V <br /> 32767 = upper range limit exceeded <br /> -32767 = lower range limit exceeded || 5001 | ||
+ | |- | ||
+ | | Analog Input 2 || AI#02 || s16 || R || 5002 | ||
+ | |- | ||
+ | | Analog Input 3 || AI#03 || s16 || R || 5003 | ||
+ | |- | ||
+ | | Analog Input 4 || AI#04 || s16 || R || 5004 | ||
+ | |- | ||
+ | | Analog Input 5 || AI#05 || s16 || R || 5005 | ||
+ | |- | ||
+ | | Analog Input 6 || AI#06 || s16 || R || 5006 | ||
+ | |- | ||
+ | | Analog Input 7 || AI#07 || s16 || R || 5007 | ||
+ | |- | ||
+ | | Analog Input 8 || AI#08 || s16 || R || 5008 | ||
+ | |} |
Revision as of 11:39, 17 July 2018
Modbus Registers
Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.
Modbus Read / Write (0x17) Function
METEL IO modules have implemented MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for: 1) Writing of outputs via MODBUS function (0x16) Write Multiple Registers 2) Reading of inputs via MODBUS function (0x03) Read Holding Registers This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the writing and reading of outputs. This requires a total of 2 frames to be sent over MODBUS.
Default Settings of Communication
Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1
Subject | Channel | Type | R/W | Value | Offset | |
---|---|---|---|---|---|---|
Measured Voltage Values |
Analog Input 1 | AI#01 | s16 | R | 1000 = 1 V 0 = 0 V -1000 = -1 V 32767 = upper range limit exceeded -32767 = lower range limit exceeded |
5001 |
Analog Input 2 | AI#02 | s16 | R | 5002 | ||
Analog Input 3 | AI#03 | s16 | R | 5003 | ||
Analog Input 4 | AI#04 | s16 | R | 5004 | ||
Analog Input 5 | AI#05 | s16 | R | 5005 | ||
Analog Input 6 | AI#06 | s16 | R | 5006 | ||
Analog Input 7 | AI#07 | s16 | R | 5007 | ||
Analog Input 8 | AI#08 | s16 | R | 5008 |