Modbus Registers

Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.

Modbus Read / Write (0x17) Function

METEL IO modules have implemented MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for: 1) Writing of outputs via MODBUS function (0x16) Write Multiple Registers 2) Reading of inputs via MODBUS function (0x03) Read Holding Registers This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the writing and reading of outputs. This requires a total of 2 frames to be sent over MODBUS.

Default Settings of Communication

Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1

Subject

Channel

Type

R/W

Value

Offset

Measured
Voltage
Values
Analog Input 1 AI#01 s16 R 1000 = 1 V
0 = 0 V
-1000 = -1 V
32767 = upper range limit exceeded
-32767 = lower range limit exceeded
5001
Analog Input 2 AI#02 s16 R 5002
Analog Input 3 AI#03 s16 R 5003
Analog Input 4 AI#04 s16 R 5004
Analog Input 5 AI#05 s16 R 5005
Analog Input 6 AI#06 s16 R 5006
Analog Input 7 AI#07 s16 R 5007
Analog Input 8 AI#08 s16 R 5008