AI8.1

From IPLOG
Revision as of 11:19, 18 July 2018 by Z013 (talk | contribs)
Jump to: navigation, search

Modbus Registers

Below is a list of available device MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.

Modbus Read / Write (0x17) Function

METEL IO modules have implemented MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for: 1) Writing of outputs via MODBUS function (0x16) Write Multiple Registers 2) Reading of inputs via MODBUS function (0x03) Read Holding Registers This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the writing and reading of outputs. This requires a total of 2 frames to be sent over MODBUS.

Default Settings of Communication

Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1

Subject Channel Type R/W Value Offset
Measured
Voltage
Values
Analog Input 1 AI#01 s16 R 1000 = 1 V
0 = 0 V
-1000 = -1 V
32767 = upper range limit exceeded
-32767 = lower range limit exceeded
5001
Analog Input 2 AI#02 s16 R 5002
Analog Input 3 AI#03 s16 R 5003
Analog Input 4 AI#04 s16 R 5004
Analog Input 5 AI#05 s16 R 5005
Analog Input 6 AI#06 s16 R 5006
Analog Input 7 AI#07 s16 R 5007
Analog Input 8 AI#08 s16 R 5008
Subject Channel Type R/W Value Offset
Measured
Current
Values
Analog Input 1 AI#11 s16 R 1000 = 1 V
0 = 0 V
-1000 = -1 V
32767 = upper range limit exceeded
-32767 = lower range limit exceeded
5011
Analog Input 2 AI#12 s16 R 5012
Analog Input 3 AI#13 s16 R 5013
Analog Input 4 AI#14 s16 R 5014
Analog Input 5 AI#15 s16 R 5015
Analog Input 6 AI#16 s16 R 5016
Analog Input 7 AI#17 s16 R 5017
Analog Input 8 AI#18 s16 R 5018
Subject Channel Type R/W Value Offset
Setting
Input
Ranges
Analog Input 1 AI#21 u16 RW 1 = ±10 V / ±30 mA
2 = ±5 V / ±20 mA
3 = ±2.5 V / ±10 mA

(1) - Default

5121
Analog Input 2 AI#22 u16 RW 5122
Analog Input 3 AI#23 u16 RW 5123
Analog Input 4 AI#24 u16 RW 5124
Analog Input 5 AI#25 u16 RW 5125
Analog Input 6 AI#26 u16 RW 5126
Analog Input 7 AI#27 u16 RW 5127
Analog Input 8 AI#28 u16 RW 5128
Subject Channel Type R/W Value Offset
States of
Relay
Outputs
COIL Relay 1 DI#01 bit R 0 = inactive
1 = active
3001
COIL Relay 2 DI#02 bit R 3002
COIL Relay 3 DI#03 bit R 3003
COIL Relay 4 DI#04 bit R 3004
Inputs DI#16 - DI#01 u16 R 0x0000 - 0x000F 3001
Subject Channel Type R/W Value Offset
Relay
Outputs
Relay Output 1 DO#01 bit RW 0 = inactive
1 = active
4001
Relay Output 2 DO#02 bit RW 4002
Relay Output 3 DO#03 bit RW 4003
Relay Output 4 DO#04 bit RW 4004
Outputs DO#16 - DO#01 u16 RW 0x0000 - 0x000F 4001