IF-14

From IPLOG
Revision as of 05:27, 17 April 2020 by Z013 (talk | contribs)
Jump to: navigation, search

Modbus Registers

Below is a list of available MODBUS registers. The same register numbers are also used by the MIOS-2 protocol.

Modbus Read / Write (0x17) Function

METEL IO modules have implemented the MODBUS function (0x17) Read/Write of Multiple registers. Typically it is required to have two separate requests (and responses) for:

1. Writing of outputs via MODBUS function (0x16) Writing Multiple Registers

2. Reading of inputs via MODBUS function (0x03) Read Holding Registers


This requires a total of 4 frames to be sent over MODBUS. If using 0x17 function only one request is needed for the reading and writing of outputs. This requires a total of 2 frames to be sent over MODBUS.


Default Settings of Communication

Device ID: 1
Baudrate: 115 200
Parity: None
Data bits: 8
Stop bits: 1

Note: The MODBUS address is the same as the address of the main device of which the IF module is part.


Subject Channel Type R/W Value Offset
IF-14G
States of
Inputs
Digital Input 1 DI#33 bit R 0 = inactive
1 = active
3033
Digital Input 2 DI#34 bit R 3034
Digital Input 3 DI#35 bit R 3035
Digital Input 4 DI#36 bit R 3036